Column Based Time Series Data
Each file imported into AspenTech Inmation via Dropzone should contain at least 2 columns. The first column of data should always contain date-time infomration and each additional column may hold values of a specific VQT items defined within the column header row(s).
To allow as much compliance with text files from different sources, different aspects of the imported file may be configured in the Object Lens for the Dropzone Datasource object. Each set of related configuration parameters is described in the following distinct sections.
Column Format
The column format is convenient for the periodic import of large amounts of historical data from different sources (e.g. a distributed series of machines producing text files).
All columns in the file must be separated by either:
-
Tabs (or "/t")
-
Semi-colons (";")
-
Commas (",")
Each column can hold the values of distinct I/O items defined within the header row(s). Header rows can also supply additional optional context information for each item. In case a specific field is left empty, the tab separator must be repeated so that the following fields have the correct number of preceding separators and are assigned correctly.
This example uses the Column Based processing option to parse a file using timestamped data, separated by a tab delimiter. The file used in this example contains ISO 8601 timestamps and can be found here.
-
Create a Dropzone Datasource object as described here.
-
Select the newly created Dropzone object and open the Object Lens panel.
-
In the Dropzone property compound, ensure that the Dropzone Processing property is set to Column Based.
-
Copy the file to the Disk Folder location specified when the Dropzone was created.
-
If the file is processed successfully, I/O Items are created under the Dropzone object in the I/O model, the names of which correspond to the column headers in the imported file. The data from each column is imported to the corresponding I/O Item along with a timestamp from the first column.
Header Rows
This section covers the different available header row formats for importing column-based time-series data. Contextual information for each I/O items can be supplied by the header row in multiple rows (multi-line column header) or in a single row (line-by-line syntax or properties enclosed in brackets). These file import options can be configured in the Dropzone datasource’s properties in the Object Lens.
Multi-line Column Header
By using multi-line column headers, multiple header rows may be supplied, each containing a specific type of context information. First, the number of header rows is configured (in the Dropzone datasource object properties using the Object Lens). Then, the assignment of each header row can be configured individually (again in the Object Lens). The following table shows a description of all the different options available for each header row assignment.
| Option | Description |
|---|---|
Altitude |
The header row contains the altitude of the I/O item defined in the 'Name' header row. |
Data Type |
The header row contains the data type of the I/O item defined in the 'Name' header row. |
Decimal Places |
The header row contains the number of decimal places for the I/O item defined in the 'Name' header row. |
Description |
The header row contains a description of the I/O item defined in the 'Name' header row. |
Engineering Unit |
The header row contains the engineering unit of the I/O item defined in the 'Name' header row. |
High Alarm Limit |
The header row contains the high alarm limit of the I/O item defined in the 'Name' header row. |
High EU Range |
The header row contains the high EU range of the I/O item defined in the 'Name' header row. |
Latitude |
The header row contains the latitude of the I/O item defined in the 'Name' header row. |
Location (Logical Name) |
the header row contains the logical location name of the I/O item defined in the 'Name' header row. |
Longitude |
The header row contains the longitude of the I/O item defined in the 'Name' header row. |
Low Alarm Limit |
The header row contains the low alarm limit of the I/O item defined in the 'Name' header row. |
Low EU Range |
The header row contains the low EU range of the I/O item in the 'Name' header row. |
Name |
The header row contains the name of the VQT item. This is the only mandatory header row since its information is used to assign the values and information of other header rows to a distinct I/O item. |
No Assignment (skip row) |
The header row is skipped. Therefore, the information in this row is not passed on to the system. |
An example and explanation is provided below:
Item1 Item2 Item3 - m3/h % psi - 200 2500 2016-04-12T12:00:00.000Z 166,98 71 1958
| In the above example, the header rows contain the I/O item name (first row), an engineering unit (second row) as well as high alarm limits (third row). The high alarm limit is not supplied for Item2, therefore two tabs are found between the two integers. The first column contains the VQT date-time information and is ignored in the header rows. The first data row with a UTC timestamp and values for all of the three items is also shown. The only mandatory header row is the 'Name' row - all other header rows are optional. |
The extra contextual information defined in these header rows is used to add property information to the created objects.
In this example, we will add contextual data that is contained in extra rows in the column header. This example uses the file found here.
-
First, create a Dropzone datasource in the I/O model as described here.
-
Select the newly created object and open the Object Lens panel.
-
In the Object Lens panel, select the Dropzone property compound and expand the drop-down menu for the Code Page property. Select the "65001 Unicode (UTF-8)" option from the drop-down.
-
Next, set the Dropzone Processing property to "Column-based time series data with UTC timestamp".
-
Then, expand the Dropzone Options property and in the Column Header Processing property, expand the drop-down menu and select Multi-Line Column Header. This is required as the column headers in the file to import are split over multiple lines.
-
For the Column Header Rows property, click the add button to add a new entry. A new entry is required for each header row in the file. In this example, 4 entries are required:
-
1 = Name
-
2 = Engineering Unit
-
3 = Latitude
-
4 = Longitude
-
-
Click Apply to save the changes.
-
Now, copy the file into the Disk Folder that was defined while configuring the Dropzone earlier.
A new folder named "work" will be displayed in this Disk Folder when the file is being processed.
-
In the I/O Model, corresponding objects should be created under the Dropzone Datasource object.
-
Select any of the newly created items under the Dropzone and using the Object Lens panel, check that the contextual Engineering Unit and Location information is specified.
Line-by-line Syntax
This syntax follows the same convention as the 'line-by-line VQT values' format (see section here covering this). Different context information of a distinct I/O item must be separated by semicolons, while each I/O item is separated by tabs. An example and exaplanation is provided below:
Item1;p(EU_UNIT)="%";p(HIGH_EU)=100 Item2;p(EU_UNIT)="m3/h" 2016-04-12T12:00:00.000Z 71 166,98
| The above header row contains the I/O item names (Item1/Item2), an engineering unit for both items and a high EU range for Item1 only. The first column contains the VQT date-time information and is ignored by the header rows. The first data row with a UTC timestamp and values for both items is also shown. A full list of available properties that may be supplied for each item can be found here. |
Properties Enclosed by Brackets
This syntax only allows optional engineering units and datatype context information to be passed on the system. Engineering units must be supplied in round bracket ('(' and ')') and datatypes must be supplied in square brackets ('[' and ']'). For example,
- Item1(m3/h)[integer] Item2 2016-04-12T12:00:00.000Z 71 356.7 - Item1[integer] Item2 2016-04-12T12:00:00.000Z 71 356.75 - Item1(m3/h) Item2 2016-04-12T12:00:00.000Z 71 356.75
Datatypes may be supplied either as textual code or as one of the four internal equivalents. All textual codes as well as available equivalents are shown in the following table. If a datatype with no equivalent ('N/A') shall be passed on to the system, textual codes need to be supplied instead.
Timestamp Options
The first column of each data row must contain date-time information. Date-time information may be supplied in one of various pre-configured formats as well as custom formats. The following table shows all of the pre-configured formats as well as an outline of how custom timestamps formats may be configured.
| Option | Example | Additional Information |
|---|---|---|
ISO8601 Timestamp in the first column |
2025-12-03T11:04:09Z |
|
Microsecond offset in the first column |
100000 |
|
Millisecond offset in the first column |
1000 |
|
Nanosecond offsets in first column |
||
No time specification in the file |
All date-time information is retreived from the file name. |
|
Picosecond offset in the first column |
1000000000 |
|
POSIX millisecond values in the first column |
1460998063000 |
|
POSIX second values in the first column |
1460998063 |
|
Second offsets in first column |
||
Timestamps according to a given format in the first column |
03.12.2025 11:04:09 |
In this case, the timestamp configuration would need to be configured manually: '%d.%m.%Y %H:%M:%S'. Day (%d), month (%m), year (%Y), hours (%H), minutes (%M), seconds (%S) and fractions of seconds (%F) or a subset need to be supplied with correct delimiters. In the example, dots ('.') are used as delimiters in the date portion of the timestamp. Colons (':') are used as delimiters in the time portion of the timestamp. |
To configure the Timestamp Options:
-
Select the Dropzone Datasource object in the I/O model panel and open the Object Lens.
-
In the Object Lens, select the Dropzone property compound and expand the Dropzone Options.
-
Expand the Timestamp Options and use the drop-down menu for the Timestamp property to select the appropriate timestamp configuration for the imported file.
-
A custom format can be defined in the Custom Format field. This is not required if the timestamps used are ISO8601-compliant.
File Name Processing
Filenames may contain information that shall be passed on to the system during file import (e.g. date-time information). Each piece of information retrieved from the file name may be configured separately. The order of the information items and a specific separator as well as the information type for each information item must be configured. The following table shows a list of available object types.
| Option | Description |
|---|---|
Equipment Model - Production Line ID |
The production line ID in the equipment model the file relates to |
Equipment Model - Work Cell ID |
The work cell ID in the equipment model that the file relate to |
Generic Information |
The information extracted at the configured position may only be used to create a node hierarchy below the Dropzone object. It will not be used for any kind of production tracking. |
Tracking - Batch ID |
The batch ID to which the data in the file relates |
Tracking - Campaign ID |
The capmpaign ID to which the data in the file relates |
Tracking - Cycling Number |
The (equipment model) cycle number the data in the file relates to |
Tracking - Lot ID |
The lot ID that the data in the file relates to |
Tracking - Machine Cycle ID |
The machine cycle ID to which the file data relates |
Tracking - Material ID |
The amterial ID to which the data in the file relates |
Tracking - Operation ID |
The operation ID that the data in the file relates to |
Tracking - Phase ID |
The phase ID that the file data relates to |
Tracking - Product ID |
The product ID that the data in the file relates to |
Tracking - Recipe ID |
The ID of the recipe or parameter set, which was used to carry out a certain production operation |
Tracking - Step ID |
The (equipment model) step ID that the data in the file relates to |
Tracking - Unitprocedure ID |
The unit procedure to which the data in the file relates |
UTC Time - Date |
The UTC timestamp data portion that file data relates to |
UTC Time - Timestamp |
The absolute UTC timestamp that the data in the file relates to |
To configure the Filename Processing options:
-
Select the Dropzone object in the I/O model and open the Object Lens.
-
In the Object Lens, select the Dropzone property compound and expand the Dropzone Options property.
-
In the Filename Processing Options, enable the "Filename holds information" checkbox. This indicates to the system that filename should be looked up for additional information.
-
Then, under Filename Information, click the
button to add a new entry.
For each entry, the Order, Separator and FilenameInfo Type must be defined.
-
If an object is required to store the information from the Filename, select "Create IoNode Object" checkbox to create an IONode object with the appropriate name.
-
Enabling the "Tracking Events" checkbox will cause the Dropzone to issue production tracking events based on the information and timestamps found.